5.8.1 Basic PID Operation
PID operates by controlling the output frequency of the inverter, through automated
system process control to maintain speed, pressure, flow, temperature and tension.
Grou
p
Code
Name
Setting
Setting Range
Unit
AP
01
Application function
selection
2
Proc PID
02
-
16
PID output monitor
-
-
-
17
PID reference monitor
-
-
-
18
PID feedback monitor
-
-
-
19
PID reference setting
50.00
-100.00100.00
%
20
PID reference source
0
Keypad
07
-
21
PID feedback source
0
V1
06
-
22
PID controller proportional
gain
50.0
0.01000.0
%
23
PID controller integral time
10.0
0.0200.0
sec
24
PID controller differential
time
0
01000
ms
25
PID controller feed-forward
compensation gain
0.0
01000
%
26
Proportional gain scale
100.0
0.0100.0
%
27
PID output filter
0
010000
ms
29
PID upper limit frequency
60.00
-300.00300.00
Hz
30
PID lower limit frequency
0.5
-300.00300.00
Hz
32
PID output scale
100.0
0.11000.0
%
33
PID output inverse
0
No
01
-
34
PID controller
motion frequency
0.00
0Max
Frequency
Hz
35
PID controller
motion level
0.0
0.0100.0
%
36
PID controller
motion delay time
600
09999
sec
37
PID sleep mode
delay time
60.0
0999.9
sec
38
PID sleep mode frequency
0.00
0Max
Frequency
Hz
39
PID wake-up level
35
0100
%
40
PID wake-up mode
selection
0
Below Level
02
-
43
PID unit gain
100.0
0300
%
44
PID unit scale
2
x 1
04
-
45
PID 2
nd
proportional gain
100.00
01000
%
In
6569
Px terminal setting options
22
I-Term Clear
052
-
23
PID