Output Terminal Delay Time Setting Details
Code and
Features
Description
OU.52 DO NC/NO
Sel
Select the contact type of relay 1 and relay 2. By setting the relevant
bit to 0, it will operate A terminal (Normally Open), and setting it to 1
will operate B terminal (Normally Closed). Shown below in the table
are Relay 1 and Relay 2 settings starting from the right bit.
Items
Bit On Status
Bit Off Status
Keypad
5.30 Base Block
This feature is used when output is blocked while operating the inverter or when the
multi-function relay must maintain the operating status by blocking output while
stopping. If the multi-function signal set as base block is entered during operation, the
motor will run freely. If the base block signal is disabled, speed search operation will
start with the value set in Cn-7275 even if the Cn-71 speed search operation
selection parameter is not activated. The output being blocked by the base block
feature does not have effect on the multi-function relay and will be recognized as
being in operation even if there is no inverter output.
Group
Code
Name
Setting
Setting Range
Unit
In
65
69
Px terminal setting options
33
Base Block
152
-
OU
31
Multi-function relay 1 item
14
Run
144
-
33
Multi-function relay 2 item
-
-