Base Block Operation Setting Details
Code and
Features
Description
In 6569 Px define
Select the multi-function input terminal to receive the base block
signal and set the applicable terminal to 33 (Base Block).
OU31 Relay 1
OU33 Relay 2
Define
Set the multi-function relay terminal to 14 (Run).
If the operation command is given, the inverter will accelerate up to
the command frequency. If the base block signal is entered during
acceleration or constant speed operation, the inverter will block the
output immediately and start free-run. If the base block signal is
disabled, the inverter will accelerate as a speed search operation until
it reaches the command frequency, without receiving a specific reset
command.
"bb" will be displayed on the keypad during the base block operation.
Disabling the base block will reset the inverter automatically and the
base block will not be recorded in the trip history.