Code and
Features
Description
CM.03 Int485
BaudR
Set a communication setting speed up to 115,200 bps.
Configuration
Function
0
1200bps
1
2400bps
2
4800bps
3
9600bps
4
19200bps
5
38400bps
6
56Kbps
7
115 Kbps (115,200 bps)
CM.04 Int485
Mode
Set a communication configuration. Set the data length, parity check
method, and the number of stop bits.
Configuration
Function
0
D8/PN/S1
8-bit data / no parity check / 1 stop bit
1
D8/PN/S2
8-bit data / no parity check / 2 stop bit
2
D8/PE/S1
8-bit data / even parity / 1 stop bit
3
D8/PO/S1
8-bit data / odd parity / 1 stop bit
CM.05 Resp
Delay
Set the response time for the slave (inverter) to react to the request
from the master. Response time is used in a system where the slave
device response is too fast for the master device to process. Set this
code to an appropriate value for smooth master-slave communication.