Code
Comm.
Address
Name
Setting
Range
Initial Value
Pro
pert
y*
V/
F
S
L
Ref.
monitor
AP-18
40
0h1812
PID feedback
monitor
(%)
0.00
-
O
O
p.125
AP-19
40
0h1813
PID reference
setting
-100.00
100.00 (%)
50.00
O
O
O
p.125
AP-20
40
0h1814
PID reference
source
0
Keypad
0:
Keypad
X
O
O
p.125
1
V1
3
V0
4
I2
5
Int 485
7
FieldBus
AP-21
40
0h1815
PID feedback
source
0
V1
0: V1
X
O
O
p.125
2
V0
3
I2
4
Int 485
6
FieldBus
AP-22
40
0h1816
PID controller
proportional
gain
0.01000.0
(%)
50.0
O
O
O
p.125
AP-23
40
0h1817
PID controller
integral time
0.0200.0
(s)
10.0
O
O
O
p.125
AP-24
40
0h1818
PID controller
differentiation
time
01000 (ms)
0
O
O
O
p.125
AP-25
40
0h1819
PID controller
feed-forward
compensation
gain
0.01000.0
(%)
0.0
O
O
O
p.125
AP-26
40
0h181 A
Proportional
gain scale
0.0100.0
(%)
100.0
X
O
O
p.125
AP-27
40
0h181B
PID output
filter
010000
(ms)
0
O
O
O
p.125
AP-28
40
0h181C
PID Mode
0
Process
PID
0
X
O
O
-
1
Normal
PID
AP-29
40
0h181D
PID upper limit
frequency
PID lower
limit
frequency
300.00 (Hz)
60.00
O
O
O
p.125
AP-30
40
0h181E
PID lower limit
frequency
-300.00
PID upper
limit
frequency(H
-60.00
O
O
O
p.125

Table of Contents

Other manuals for LSIS G100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS G100 and is the answer not in the manual?

LSIS G100 Specifications

General IconGeneral
BrandLSIS
ModelG100
CategoryInverter Drive
LanguageEnglish

Related product manuals