Inspection
Area
Inspectio
n Item
Inspection
Details
Inspection
Method
Judgment
Standard
Inspection
Equipment
Input/Output
circuit
All
Megger test
(between
input/output
terminals and
earth terminal)
Disconnect
inverter and
short
R/S/T/U/V/W
terminals,
and then
measure
from each
terminal to
the ground
terminal
using a
Megger.
Must be
above 5 MΩ
DC 500 V
Megger
Is there anything
loose in the
device?
Tighten up all
screws.
No
abnormality
Is there any
evidence of parts
overheating?
Visual
inspection
Connectio
n
conductor
/cable
Are there any
corroded cables?
Visual
inspection
No
abnormality
-
Is there any
damage to cable
insulation?
Terminal
block
Is there any
damage?
Visual
inspection
No
abnormality
-
Smoothing
capacitor
Measure
electrostatic
capacity.
Measure with
capacity
meter.
Rated
capacity over
85%
Capacity
meter
Relay
Is there any
chattering noise
during operation?
Visual
inspection
No
abnormality
-
Is there any
damage to the
contacts?
Visual
inspection
Braking
resistor
Is there any
damage from
resistance?
Visual
inspection
No
abnormality
Digital
multimeter /
analog tester
Check for
disconnection
Disconnect
one side and
measure with
a tester.
Must be
within ±10%
of the rated
value of the
resistor.
Control
circuit
Operation
check
Check for output
voltage
imbalance while
Measure
voltage
between the
Balance the
voltage
between
Digital
multimeter or

Table of Contents

Other manuals for LSIS G100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS G100 and is the answer not in the manual?

LSIS G100 Specifications

General IconGeneral
BrandLSIS
ModelG100
CategoryInverter Drive
LanguageEnglish

Related product manuals