EasyManuals Logo

LSIS G100 User Manual

LSIS G100
343 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #311 background imageLoading...
Page #311 background image
Inspection
Area
Inspectio
n Item
Inspection
Details
Inspection
Method
Judgment
Standard
Inspection
Equipment
Protection
circuit
the inverter is in
operation.
inverter
output
terminal
U/V/W.
phases: within
4 V for 200 V
series and
within 8 V for
400 V series.
DC voltmeter
Is there an error
in the display
circuit after the
sequence
protection test?
Test the
inverter
output
protection in
both short
and open
circuit
conditions.
The circuit
must work
according to
the sequence.
Cooling
system
Cooling
Fan
Are any of the
fan parts loose?
Check the
connecting
part of the
connector.
No
abnormality
-
Display
Display
device
Is the display
value normal?
Check the
command
value on the
display
device.
Specified and
managed
values must
match.
Voltmeter,
ammeter, etc.
10.1.3 Bi-annual Inspections
Inspection
area
Inspection
item
Inspection
details
Inspection
method
Judgment
standard
Inspection
equipment
Motor
Insulation
resistance
Megger test
(between the
input, output and
earth terminals).
Disconnect
the cables for
terminals
U/V/ W and
test the
wiring.
Must be
above 5 MΩ
DC 500 V
Megger
Do not run an insulation resistance test (Megger) on the control circuit as it may result in
damage to the product. This may cause damage to the inverter.
10.2 Storage and Disposal

Table of Contents

Other manuals for LSIS G100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS G100 and is the answer not in the manual?

LSIS G100 Specifications

General IconGeneral
BrandLSIS
ModelG100
CategoryInverter Drive
LanguageEnglish

Related product manuals