EasyManuals Logo

Mircom PRO-2000 Series User Manual

Mircom PRO-2000 Series
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #87 background imageLoading...
Page #87 background image
PRO-2000 Installation and Operation Manual
81
LCD Panel Operations - Menu Mode
The buttons on the System Keypad are used mainly for maintenance functions at access level 1 and 2.
•The numbers are used to select menu options and used as a generic numeric keypad for operations such as setting the
clock.
Enter push button confirms the keyed information.
Exit push button aborts the current command and returns to the previous menu. Depressing the Exit push button instead of
the Enter push button causes the panel to leave the current function and disregard any previously entered values.
Continue push button confirms selection. The system, in some instances, prompts to depress this push button before going
to another step.
Menu push button activates the main system menu selection list.
Help push button displays context sensitive help.
Arrow push buttons move the cursor across the text displays on the LCD, scroll through menus, and tab over selections.
When the Menu push button from the System keypad is pressed and he PRO-2000 is set at Access Level 1 or 2, the system goes
into Menu Mode. This mode allows access to various menus to enter information in the system. The Main Menu offers eight options:
Event Log option Displays, prints, and clears the Event Log.
Access Level option Sets access protection level 2 (using a password).
Set Clock option Sets the system date and time.
Panel Brightness Adjusts the intensity of the LCD and LEDs.
Control option
Maintenance option Place part or all of the PRO-2000 in Service and Isolate Mode, to manually activate and deactivate
outputs, to put a stub or loop back in service. Removing a zone from Isolate places the devices in
Service mode for verification of the state of the devices.
The system automatically exits the Menu Mode if a new event occurs, for example, a new Alarm, Supervisory, or Status event, or
if no push button is depressed for more than 5 minutes.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom PRO-2000 Series and is the answer not in the manual?

Mircom PRO-2000 Series Specifications

General IconGeneral
BrandMircom
ModelPRO-2000 Series
CategoryControl Systems
LanguageEnglish

Related product manuals