874
APPX
Appendix 8 How to Use CPU Module Logging Configuration Tool
Save
The following window configures the target storage for data logging file and switching timing of storage files. ( Page 183
Switching to a storage file)
Item Description Setting range Default
Logging
file save
setting
File save destination Specify the storage folder for the data logging file. 60 characters or less (double-
byte character not allowed)
LOG
[Logging
setting No.]
Folder to store file to be saved Select information to be added to the name of the folder
which stores the storage file.
Not checked
File name Simple setting Specify information to be added to the name of the
storage file (the name of the storage folder, date, time) by
using the [Simply set additional information] button.
Checked
Optional setting Specify the format of information to be added to the name
of the storage file (the name of the storage folder, date,
time) by using the [Optionally set additional information]
button. The device data value can be added.
*3
*1*2
Add date type Add date/time when the file switching condition is satisfied
and when the file is created if the simple setting or
optional setting is selected.
File
switching
setting
Number of
files to be
saved
Number of files to be
saved
Specify the maximum number of storage files. 1 to 65535 1
Operation when
exceeds the number
of files
Select the operation when the number of files exceeds the
maximum number of files to be saved. ( Page 186
Action to take when the maximum number of storage files
is exceeded)
•Overwrite
•Stop
Overwrite
File switch timing
*4
Select the timing at which the file is replaced with new one
(Page 184 File switching condition)
• Number of records: 1 to
65500
• File size: 10 to 16384K bytes
• Condition specification
Number of
records
(1000)