96
6 Examination of System Configuration
6.6 Expansion of FX2N Series I/O Powered Extension Unit (Calculation of Current Consumption)
2 Check the current capacity of the 24V DC service power supply based on the
value shown in the quick reference matrix.
1. In the case of AC power supply/DC input type
The remaining power supply capacity (current) can be used as a power supply to loads (sensors or the like).
When special adapters and special function units/blocks are connected by external wiring, it is necessary to
consider whether they can be covered by the remaining power supply capacity.
2. In the case of DC power supply/DC input type
24V DC service power supply is not provided.
3. In the case of AC power supply/AC input type
24V DC service power supply is not provided.
3 When the power supply capacity is insufficient, connect another input/output
powered extension unit.
When two input/output powered extension units or more are connected, calculate the power supply
capacities of the input/output extension blocks and special function units/blocks connected to them,
and check the capacity.

Table of Contents

Other manuals for Mitsubishi FX3U Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U Series and is the answer not in the manual?

Mitsubishi FX3U Series Specifications

General IconGeneral
ModelFX3U Series
Program Memory64k steps
Execution Speed0.065 μs/basic instruction
TypePLC (Programmable Logic Controller)
Power Supply100-240V AC
I/O PointsUp to 384
CommunicationUSB
ExpansionSupported via expansion modules
High-Speed CountersUp to 6 channels
Analog Input/OutputAvailable via expansion modules
Temperature Range0 to 55°C
Programming LanguageLadder Logic, Structured Text
Built-in FunctionsPID control
Humidity5 to 95% (non-condensing)