FX3U Series Programmable Controllers
User’s Manual - Hardware Edition
156
9 Preparation for Wiring and Power Supply Wiring Procedures
9.4 Grounding
9.4 Grounding
Ground the PLC as stated below.
Perform class D grounding. (Grounding resistance: 100 or less)
Ground the PLC independently if possible.
If it cannot be grounded independently, ground it jointly as shown below.
Extension devices of PLC (except expansion board and special communication/high-speed input/output
adapter)
Use ground wires thicker than AWG14 (2 mm
2
).
Position the grounding point as close to the PLC as possible to decrease the length of the ground wire.
PLC
Another
equipment
PLC
Another
equipment
PLC
Another
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition
Expansion
board
Input/output
extension unit
Main unit
Special
adapter
Special
extension
Another
equipment
PLC
Independent grounding
Class D grounding
(grounding resistance : 100
or less)

Table of Contents

Other manuals for Mitsubishi FX3U Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U Series and is the answer not in the manual?

Mitsubishi FX3U Series Specifications

General IconGeneral
ModelFX3U Series
Program Memory64k steps
Execution Speed0.065 μs/basic instruction
TypePLC (Programmable Logic Controller)
Power Supply100-240V AC
I/O PointsUp to 384
CommunicationUSB
ExpansionSupported via expansion modules
High-Speed CountersUp to 6 channels
Analog Input/OutputAvailable via expansion modules
Temperature Range0 to 55°C
Programming LanguageLadder Logic, Structured Text
Built-in FunctionsPID control
Humidity5 to 95% (non-condensing)

Related product manuals