7 Functions and settings
116 TAPCON® 230 basic 2117246/02 EN © Maschinenfabrik Reinhausen 2012
Setting range Step size Factory setting
0 A – 9999 A 1 A 0 A
Table 34 Setting range for primary transformer current
To set the primary transformer current, proceed as follows:
1. > Configuration > Transformer
data > 2x
.
<02> Primary Current.
2. Press
to highlight a digit.
The digit position you want is highlighted
and the value can be changed.
3. Press
to increase the value or to
reduce it.
4. Press
.
The primary transformer current is set.
7.4.1.4 Setting the current transformer connection
To obtain a correct display, you must select a current transformer connection.
While "Unknown" is set for the current transformer connection, the current is
displayed as a percentage in relation to the selected measurement input. If
you select a current transformer connection, the absolute value (in amps) is
displayed.
The following values can be set:
1 A
5 A