7 Functions and settings
128 TAPCON® 230 basic 2117246/02 EN © Maschinenfabrik Reinhausen 2012
A continuous pulse is output if you set the raise/lower switching pulse duration
to 0.
If the motor-drive unit does not start using the default setting (1.5 seconds),
then please increase the pulse time.
Setting range Step size Factory setting
0 s...10 s 0.1 s 1.5 s
Table 36 Setting range for raise/lower switching pulse time
To set the switching pulse time, proceed as follows:
1. > Configuration > General >
3x
.
<03> R/L pulse duration.
2. Press
or to to set the pulse dura-
tion.
3. Press
.
The switching pulse time is set.
7.4.2.5 Setting operation counter
The device is fitted with an internal operation counter. In this screen you can
set the number of tap-change operations for comparing with the operation
counter of the motor-drive unit for example.
To ensure correct operation counter function, the "Motor running" signal of
the motor-drive unit must be connected with a configurable input (GPI 1...6)
and then the "Motor running" function assigned to this input (see
"Configurable inputs and outputs" on page 135).
Setting range Step size Factory setting
0...99999999 1 0
Table 37 Switching operation counter setting range