Page #117 background imageLoading...
Page #117 background image
NTI ENTERPRISE ENVIRONMENT MONITORING SYSTEM
108
Figure 121- Smart Alert configuration- continued
Smart Alert Notifications
Notify Again Time Enter the amount of time in seconds, minutes, or hours (1-999) before an alert message will be
repeated
Notify on Return to Normal The user can also be notified when the Smart Alert conditions have returned to the normal (non-
triggered state) by selecting the "Notify when return to normal" box.
Auto Acknowledge Place a checkmark in this box to have alert notifications in the summary page return to normal
state automatically when Smart Alert conditions return to normal.
Enable Syslog Alerts Place a checkmark in this box to have alert notifications sent via Syslog messages
Enable SNMP traps Place a checkmark in this box to have alert notifications sent via SNMP traps (v2c)
Enable Email Alerts Place a checkmark in this box to have alert notifications sent via Email
Email Subject Enter the subject to be viewed when an email alert message is received
Select IP Camera Associate an Event with an IP camera. Select an IP camera from the drop-down box.
Attach IP Camera capture to
email
An image will be captured and sent with the alert message when an alert is sent via e-mail. IP
cameras that are monitored by the ENVIROMUX (page 61) will be available for this purpose.
Note: To be able to send IP camera captures as e-mail attachments, viewer security (in
your camera’s configuration) needs to be disabled. Consult your IP camera manual to
see if this feature is present and for instructions on how to do this.
Save image to USB Save the image captured by the IP camera to a connected USB Flash Drive
Enable SMS Alerts
Place a checkmark in this box to have alert notifications sent via SMS messages (requires a
modem)
Enable Siren Turn ON the siren when this event goes to alert (E-16D only)
Enable Beacon Turn ON the beacon when this event goes to alert (E-16D only)
Smart Alert Command
Associated Output Relay Associate the Smart Alert with the operation of the output relay, or not
Note: Only one sensor or Smart Alert should be associated with the Output Relay at a
time. Contradicting commands from two or more sensors or Smart Alerts will result in
the output relay responding to the state directed by the last command received.
Output Relay Status on Alert State the output relay will be in when a Smart Alert is triggered
Output Relay Status on Return
from Alert
State the output relay will be in when a Smart Alert is no longer being triggered

Table of Contents

Other manuals for NTI ENVIROMUX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NTI ENVIROMUX Series and is the answer not in the manual?

NTI ENVIROMUX Series Specifications

General IconGeneral
Product TypeEnvironmental Monitoring System
Temperature Range-40°C to 85°C
Power Supply12V DC or 24V AC
Network InterfaceEthernet 10/100 Mbps
Alarm NotificationsEmail, SNMP
Sensor Types SupportedTemperature, Humidity, Water, Airflow
Power12V DC or 24V AC
Operating Temperature-40°C to 85°C
MountingWall or Rack Mount
Communication InterfacesEthernet
Data LoggingYes
ComplianceCE, RoHS