NTI ENTERPRISE ENVIRONMENT MONITORING SYSTEM
36
Internal Sensors
E-16D and -5D have three on-board sensors, which are permanently present:
- one temperature sensor
- one humidity sensor
- one power (battery) sensor
Internal sensors are monitored and fully configurable just as External Sensors are (see Figure 37 and page 42) except that they
do not have a box for "Enable Disconnection Alert" since they cannot be disconnected.
The internal temperature sensor and humidity sensor also include an Offset feature. These sensors measure the internal
environment of the ENVIROMUX, however that value may be different than the environment the ENVIROMUX is actually mounted
in. If you know what the difference is, you can use the "Offset" block to enter a value, positive or negative, and that will be
applied to the measured value. The resulting difference will be the temperature or humidity that is reported on the Summary page.
For example, if the measured temperature is 75˚F, and the environment is typically 5 degrees cooler, enter a value of "-5", click
"Save", and the reported value will now be 70˚F.
Internal sensors are always shown in the left menu of the web page and they cannot be removed.
Figure 35- Internal Sensor Configuration