NTI ENTERPRISE ENVIRONMENT MONITORING SYSTEM
36
Internal Sensors
E-16D and -5D have three on-board sensors, which are permanently present:
- one temperature sensor
- one humidity sensor
- one power (battery) sensor
Internal sensors are monitored and fully configurable just as External Sensors are (see Figure 37 and page 42) except that they
do not have a box for "Enable Disconnection Alert" since they cannot be disconnected.
The internal temperature sensor and humidity sensor also include an Offset feature. These sensors measure the internal
environment of the ENVIROMUX, however that value may be different than the environment the ENVIROMUX is actually mounted
in. If you know what the difference is, you can use the "Offset" block to enter a value, positive or negative, and that will be
applied to the measured value. The resulting difference will be the temperature or humidity that is reported on the Summary page.
For example, if the measured temperature is 75˚F, and the environment is typically 5 degrees cooler, enter a value of "-5", click
"Save", and the reported value will now be 70˚F.
Internal sensors are always shown in the left menu of the web page and they cannot be removed.
Figure 35- Internal Sensor Configuration

Table of Contents

Other manuals for NTI ENVIROMUX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NTI ENVIROMUX Series and is the answer not in the manual?

NTI ENVIROMUX Series Specifications

General IconGeneral
Product TypeEnvironmental Monitoring System
Temperature Range-40°C to 85°C
Power Supply12V DC or 24V AC
Network InterfaceEthernet 10/100 Mbps
Alarm NotificationsEmail, SNMP
Sensor Types SupportedTemperature, Humidity, Water, Airflow
Power12V DC or 24V AC
Operating Temperature-40°C to 85°C
MountingWall or Rack Mount
Communication InterfacesEthernet
Data LoggingYes
ComplianceCE, RoHS

Related product manuals