4-48
4-2 Function Mode
4
Functions
•By allocating 08 (SET) or 53 (SP-SET) to the desired multi-function input and then turning on/off
the SET or SP-SET terminal, you can switch and control two different motors.
•Switch to the 2nd control function at the SET terminal after turning off the RUN command and the
Inverter output.
•You can switch to the 2nd control function at the SP-SET terminal while in operation..
•To display and set each parameter for the 2nd control (parameter No.200s), allocate SET and SP-
SET.
•Parameters changeable while in operation are as follows:
Inverter
U/T1
V/T2
W/T3
SET
/SP-SET
L
Motor
1
Motor
2
Parameter No. Function name
Selection
SET SP-SET
F002/F202 Acceleration time 1 Yes Yes
F003/F203 Deceleration time 1 Yes Yes
A001/A201 Frequency reference selection No Yes
A002/A202 RUN command selection No Yes
A003/A203 Base frequency No Yes
A004/A204 Maximum frequency No Yes
A020/A220 Multi-step speed reference 0 Yes Yes
A041/A241 Torque boost selection No Yes
A042/A242 Manual torque boost voltage Yes Yes
A043/A243 Manual torque boost frequency Yes Yes
A044/A244 V/f characteristics selection No Yes
A045/A245 Output voltage gain No Yes
A061/A261 Frequency upper limit Yes Yes
A062/A262 Frequency lower limit Yes Yes
A092/A292 Acceleration time 2 Yes Yes
A093/A293 Deceleration time 2 Yes Yes
A094/A294 2-step acceleration/deceleration selection Yes Yes
A095/A295 2-step acceleration frequency Yes Yes
A096/A296 2-step deceleration frequency Yes Yes