4-86
4-2 Function Mode
4
Functions
1176h
Overvoltage protection 
function selection during 
deceleration
b133 R/W
00: Disabled
01: Enabled
⎯
1177h
Overvoltage protection level 
setting during deceleration
b134 R/W
200-V class: 330. to 395. 
400-V class: 660. to 790.
1. [V]
10F7h
Overcurrent suppression 
function
b140 R/W
00: Disabled
01: Enabled
⎯
10F8h Automatic carrier reduction b150 R/W
00: Disabled
01: Enabled
⎯
10F9h Ready function selection b151 R/W
00: RDY disabled
01: RDY enabled
⎯
1103h
Multi-function input 1 
selection
C001 R/W
00: FW/01: RV/02: CF1/03: CF2/04: 
CF3/05: CF4/06: JG/07: DB/08: SET/09: 
2CH/11: FRS/12: EXT/13: USP/15: SFT/
16: AT/18: RS/19: PTC terminal 5 only/
20: STA/21: STP/22: F/R/23: PID/24: 
PIDC/27: UP/28: DWN/29: UDC/31: 
OPE/50: ADD/51: F-TM/52: RDY/53: 
SP-SET/64: EMR(automatically 
allocated to terminal 3 if enabled)/255: 
NO
⎯
1532h
2nd multi-function input 1 
selection
C201 R/W
1104h
Multi-function input 2 
selection
C002 R/W
1533h
2nd multi-function input 2 
selection
C202 R/W
1105h
Multi-function input 3 
selection
C003 R/W
1534h
2nd multi-function input 3 
selection
C203 R/W
1106h
Multi-function input 4 
selection
C004 R/W
1535h
2nd multi-function input 4 
selection
C204 R/W
1107h
Multi-function input 5 
selection
C005 R/W
1536h
2nd multi-function input 5 
selection
C205 R/W
110Bh
Multi-function input 1 
operation selection
C011 R/W
00: NO
01: NC
⎯
110Ch
Multi-function input 2 
operation selection
C012 R/W
110Dh
Multi-function input 3 
operation selection
C013 R/W
110Eh
Multi-function input 4 
operation selection
C014 R/W
110Fh
Multi-function input 5 
operation selection
C015 R/W
1114h
Multi-function output 
terminal 11 selection
C021 R/W
00: RUN/01: FA1/02: FA2/03: OL/04: 
OD/05: AL/06: Dc/07: FBV/08: NDc/09: 
LOG/10: ODc(Do not use.)/43: LOC
⎯
1119h
Relay output (AL2, AL1) 
function selection
C026 R/W
111Bh AM selection C028 R/W
00: F (Output frequency)
01: A (Output current)
⎯
111Dh
Multi-function output 
terminal 11 contact selection
C031 R/W
00: NO
01: NC
⎯
1122h
Relay output (AL2, AL1) 
contact selection
C036 R/W
00: NO
01: NC
⎯
Register 
No.
Function name
Parameter 
No.
R/W
Function
Monitor or data range
Resolution