App-10
Appendix-1 Parameter List
Restart during momentary power interruption
b001 Retry selection
00: Alarm
01: 0 Hz start
02: Frequency Matching start
03: Trip after Frequency Matching
deceleration stop
00 No
b002
Allowable
momentary power
interruption time
0.3 to 25.0 1.0 No s
b003 Retry wait time 0.3 to 100.0 1.0 No s
b004
Momentary power
interruption/
undervoltage trip
during stop
selection
00: Disabled
01: Enabled
00 No
b005
Momentary power
interruption retry
time selection
00: 16 times
01: No limit
00 No
b011
Starting frequency
at Active
Frequency
Matching restart
00: Frequency at interruption
01: Max. frequency
02: Set frequency
00 No
Electronic thermal
b012
Electronic thermal
level
0.2 × Rated current to 1.0 × Rated current
Rated
current
No A
b212
*2nd electronic
thermal level
Rated
current
b013
Electronic thermal
characteristics
selection
00: Reduced torque characteristics 1
01: Constant torque characteristics
02: Reduced torque characteristics 2
00
No
b213
*2nd electronic
thermal
characteristics
selection
00
Parameter
No.
Function name
Monitor or data range
(Digital Operator)
Default
setting
Changes
during
operation
Unit
Set
value
* 2nd control is displayed when SET (08) is allocated to one of from C001 to C005.