App-11
Appendix-1 Parameter List
Overload limit
b021
Overload limit 
selection
00: Disabled
01: Enabled in acceleration/constant speed 
operation
02: Enabled in constant speed operation
01
No ⎯
b221
*2nd overload limit 
selection
01
b022
Overload limit 
level
0..1 × Rated current to 1.5 × Rated current
1.5 × 
Rated 
current
No A
b222
*2nd overload limit 
level
1.5 × 
Rated 
current
b023
Overload limit 
parameter
0.1 to 3000.0
1.0
No s
b223
*2nd overload limit 
parameter
1.0
b028
Overload limit 
source selection
00: b022, b222 set values
01: Input terminal O
00
No ⎯
b228
*2nd overload limit 
source selection
00
Active Frequency Matching
b029
Deceleration rate 
constant at Active 
Frequency 
Matching restart
0.1 to 3000.0 0.5 No s
b030
Active Frequency 
Matching restart 
level
0.2 × Rated current to 2.0 × Rated current
Rated 
current
No A
Lock
b031 Soft lock selection
00: Data other than b031 cannot be changed 
when terminal SFT is ON.
01: Data other than b031 and the specified 
frequency parameter cannot be changed 
when terminal SFT is ON.
02: Data other than b031 cannot be changed.
03: Data other than b031 and the specified 
frequency parameter cannot be changed.
10: Data other than parameters changeable 
during operation cannot be changed.
01 No ⎯
Parameter 
No.
Function name
Monitor or data range
(Digital Operator)
Default 
setting
Changes 
during 
operation
Unit
Set 
value
* 2nd control is displayed when SET (08) is allocated to one of from C001 to C005.