App-12
Appendix-1 Parameter List
Non-stop function at momentary power interruption
b050
Selection of non-
stop function at 
momentary power 
interruption 
00: Disabled
01: Enabled (Stop)
02: Enabled (Restart)
00 No
b051
Starting voltage of 
non-stop function 
at momentary 
power interruption
0.0 to 1000. 0.0 No V
b052
Stop deceleration 
level of non-stop 
function at 
momentary power 
interruption
0.0 to 1000. 0.0 No V
b053
Deceleration time 
of non-stop 
function at 
momentary power 
interruption
0.01 to 99.99
100.0 to 999.9
1000 to 3000
1.0 No s
b054
Deceleration 
starting width of 
non-stop function 
at momentary 
power interruption
0.0 to 10.0 0.0 No Hz
Others
b055
Overvoltage 
protection 
proportional gain 
during 
deceleration
0.2 to 5.0 0.2 Yes ⎯
b056
Overvoltage 
protection integral 
time during 
deceleration
0.0 to 150.0 0.2 Yes s
b080 AM adjustment
0. to 255.
(Shared with C086 for AM offset adjustment)
100. Yes ⎯
b082 Starting frequency 0.5 to 9.9 1.5 No Hz
b083 Carrier frequency 2.0 to 12.0 3.0 No kHz
Initialization
b084
Initialization 
selection
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes data
00 No ⎯
b085
Initialization 
parameter 
selection
00
* Do not change.
00 No ⎯
Parameter 
No.
Function name
Monitor or data range
(Digital Operator)
Default 
setting
Changes 
during 
operation
Unit
Set 
value
* 2nd control is displayed when SET (08) is allocated to one of from C001 to C005.