EasyManua.ls Logo

Omron JX

Omron JX
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-22
2-2 Wiring
2
Design
Functions and Connections of the Control Circuit Terminals
*1. Simultaneous input of current and voltage is not possible. Do not connect the signal lines simultaneously.
*2.
By factory default, multi-function output 11 is set to NO contact. To switch to NC contact, change the C031
setting.
*3. Do not input negative voltage. Doing so may result in damage to the inverter
Terminal
function
Terminal
symbol
Terminal name Function and connecting method Wire size
Contact
input
(for
switching
function)
1
2
3
4
5
Multi-function
input
Select functions and allocate them to terminals 1 to 5.
(The figure below illustrates the wiring of the sink logic.)
Shield wire
of 0.14 to
0.75 mm
2
Recomme
nded wire
size:
0.75 mm
2
Power
supply
P24 Internal 24 V DC 24 V DC output
L Input common Input signal common
PCS
Input power
supply
If the multi-function input is set as the sink logic, the PCS
terminal acts as an external power supply input terminal.
If the multi-function input terminal is set as the source logic,
the PCS terminal acts as an internal power supply output
terminal.
External
analog
frequency
reference
H
Frequency
reference power
supply output
External voltage directive is 0 to 9.8 V.
(Nominal input: 10 V)
*1
O
*3
Frequency
reference Input
(Voltage
directive)
OI
*4
Frequency
reference Input
(Current
directive)
L
Frequency
reference
common
Monitor
output
AM
Multi-function
analog output
Choose from frequency or output current.
Output terminal specifications
0 to 10 V DC full-scale
1 mA max.
Open
Collector
Output
11
Multi-function
output
*2
Output terminal specifications
Between each terminal and PC the
voltage drop is 4V max. at power-on
Open collector output
27 V DC max.
50 mA max.
Select the status of the Inverter and allocate it to terminal 11.
CM2
Multi-function
output common
Relay
output
AL2
AL1
Relay output
Selection of functions is the same as the multi-function
output.
*5 *6
AL0
Relay output
common
L 5 4 3 2 1
H OOI L
Variable resistor
(1 or 2 W min.)
1 to 2 kΩ
H
O
OI
L
+
-
0 to 9.8 V DC
(Nominal input: 10 V)
Input impedance 10 kΩ
H
O
OI
L
-
+
4 to 19.6 mA DC
(Nominal input: 20 mA)
Input impedance 250 Ω
AM
L
CM2
11
RY

Table of Contents

Other manuals for Omron JX