3-19
3-6 Parameter List
3
Operation
Multi-step speed, Jogging
A020
Multi-step speed
reference 0
0.0/Starting frequency to Max. frequency 6.0 Yes Hz 1029 4-12
A220
*2nd multi-step
speed reference 0
0.0/Starting frequency to 2nd max. frequency 6.0 Yes Hz 150F 4-12
A021
Multi-step speed
reference 1
0.0/Starting frequency to Max. frequency
0.0
Yes Hz
102B
4-12
A022
Multi-step speed
reference 2
0.0 102D
A023
Multi-step speed
reference 3
0.0 102F
A024
Multi-step speed
reference 4
0.0 1031
A025
Multi-step speed
reference 5
0.0 1033
A026
Multi-step speed
reference 6
0.0 1035
A027
Multi-step speed
reference 7
0.0 1037
A028
Multi-step speed
reference 8
0.0 1039
A029
Multi-step speed
reference 9
0.0 103B
A030
Multi-step speed
reference 10
0.0 103D
A031
Multi-step speed
reference 11
0.0 103F
A032
Multi-step speed
reference 12
0.0 1041
A033
Multi-step speed
reference 13
0.0 1043
A034
Multi-step speed
reference 14
0.0 1045
A035
Multi-step speed
reference 15
0.0 1047
A038 Jogging frequency 0.00/Starting frequency to 9.99 6.00 Yes Hz 1048 4-14
A039
Jogging stop
selection
00: Free-run stop
01: Deceleration stop
02: DC injection braking stop
00 No 1049 4-14
Charact. Torque boost
A041
Torque boost
selection
00: Manual torque boost only
01: Automatic (simple) torque boost
00
No -
104A
4-15
A241
*2nd torque boost
selection
00 1510
A042
Manual torque boost
voltage
0.0 to 20.0
5.0
Yes %
104B
4-15
A242
*2nd manual torque
boost voltage
0.0 1511
Parameter
No.
Function name
Monitor or data range
(Digital Operator)
Default
setting
Change
during
Run
Unit
Modbus
Address
(Hex)