3-6 Parameter List
3
Operation
PID control
A077 Reverse PID function
00: OFF (Deviation = Target value - Feedback
value)
01: ON (Deviation = Feedback value - Target
value)
00 No ⎯ 106E 4-22
A078
PID output limit
function
0.0 to 100.0 0.0 No % 106F 4-22
AVR
A081 AVR selection
00: Always ON
01: Always OFF
02: OFF during deceleration
02 No ⎯ 1070 4-26
A082
AVR voltage
selection
200-V class: 200/215/220/230/240
400-V class: 380/400/415/440/460/480
200/400 No V 1071 4-26
RUN mode, Acceleration/Deceleration functions
A085 RUN mode selection
00: Normal operation
01: Energy-saving operation
00 No - 1072 4-26
A086
Energy-saving
response/accuracy
adjustment
0 to 100 50 No % 1073 4-26
A092 Acceleration time 2
0.01 to 99.99
100.0 to 999.9
1000. to 3000.
15.00
Yes s
1074 M
1075 L
4-27
A292
*2nd acceleration
time 2
15.00
1519 M
151A L
A093
Deceleration
time 2
0.01 to 99.99
100.0 to 999.9
1000. to 3000.
15.00
Yes s
1076 M
1077 L
4-27
A293
*2nd deceleration
time 2
15.00
151B M
151C L
A094
2-step
accel/decel selection
00: Switched via multi-function input 09 (2CH)
01: Switched by setting
00
No ⎯
1078
4-27
A294
*2nd 2-step
accel/decel selection
00 151D
A095
2-step acceleration
frequency
0.0 to 400.0
0.0
No Hz
107A
4-27
A295
*2nd 2-step
acceleration
frequency
0.0 151F
A096
2-step deceleration
frequency
0.0 to 400.0
0.0
No Hz
107C
4-27
A296
*2nd 2-step
deceleration
frequency
0.0 1521
A097
Acceleration pattern
selection
00: Line
01: S-shape curve
00 No ⎯ 107D 4-28
A098
Deceleration pattern
selection
00: Line
01: S-shape curve
00 No ⎯ 107E 4-28
External frequency adjust
A101 OI start frequency 0.0 to 400.0 0.0 No Hz 1080
4-11
4-28
A102 OI end frequency 0.0 to 400.0 0.0 No Hz 1082
4-11
4-28
A103 OI start ratio 0. to 100. 0. No % 1083
4-11
4-28
A104 OI end ratio 0. to 100. 100. No % 1084
4-11
4-28
A105 OI start selection
00: Use OI start frequency [A101]
01: 0 Hz start
01 No ⎯ 1085
4-11
4-28
Parameter
No.
Function name
Monitor or data range
(Digital Operator)
Default
setting
Change
during
Run
Unit
Modbus
Address
(Hex)
Page