1141
Failure Diagnosis Instructions Section 3-30
Generating or Clearing User-defined Non-fatal Errors
The following table shows the function of the operands.
Note The value of operand N must be different from the content of A529
(the system-generated FAL/FALS number).
Note *Other settings would be constants #0200 through #FFFE or a word address.
Generating Non-fatal System Errors (CS1-H, CJ1-H, CJ1M, or CS1D Only)
The following table shows the function of the operands.
Note The value of operand N must be the same as the content of A529
(the system-generated FAL/FALS number).
Operand Specifications
N S Function
0 #0001 to #01FF Clears the non-fatal error with the correspond-
ing FAL number.
#FFFF Clears all non-fatal errors.
Other* Clears the most serious non-fatal error.
1 to 511
(These FAL num-
bers are shared
with FALS num-
bers.)
#0000 to #FFFF Generates a non-fatal error with the corre-
sponding FAL number (no message).
Word address Generates a non-fatal error with the corre-
sponding FAL number.
The 16-character ASCII message contained in
S through S+7 will be displayed on the Pro-
gramming Device.
Operand Function
N 1 to 511 (These FAL numbers are shared with FALS numbers.)
S Error code that will be generated. (See Description below.)
S+1 Error details code that will be generated. (See Description below.)
Area N S
CIO Area --- CIO 0000 to CIO 6143
Work Area --- W000 to W511
Holding Bit Area --- H000 to H511
Auxiliary Bit Area --- A000 to A959
Timer Area --- T0000 to T4095
Counter Area --- C0000 to C4095
DM Area --- D00000 to D32767
EM Area without bank --- E00000 to E32767
EM Area with bank --- En_00000 to En_32767
(n = 0 to C)
Indirect DM/EM
addresses in binary
--- @ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
--- *D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants 0 to 511 #0000 to #FFFF