242
Timer and Counter Instructions Section 3-6
Applicable Program Areas
Description Program BREAK(514) between FOR(512) and NEXT(513) to cancel the
FOR-NEXT loop when BREAK(514) is executed. When BREAK(514) is exe-
cuted, the rest of the instructions up to NEXT(513) are processed as
NOP(000).
Flags
Precautions A BREAK(514) instruction cancels only one loop, so several BREAK(514)
instructions (the number of levels nested) are required to escape from nested
loops.
BREAK(514) can be used only in a FOR-NEXT loop.
3-6 Timer and Counter Instructions
This section describes instructions used to define and handle timers and
counters.
Note TIMU(541), TIIMUX(556), TMUH(544), and TMUHX(557) are supported by
CJ1-H-R CPU Units only.
Block program areas Step program areas Subroutines Interrupt tasks
Not allowed OK OK OK
N repetitions
Condition a ON
Processed as NOP(000).
Repetitions
forced to end.
Name Label Operation
Error Flag ER OFF
Equals Flag = OFF
Negative Flag N OFF
Instruction Mnemonic Function code Page
HUNDRED-MS TIMER TIM/TIMX ---/551 245
TEN-MS TIMER TIMH/TIMHX 015/551 249
ONE-MS TIMER TMHH/TIMHHX 540/552 253
TENTH-MS TIMER (See note.) TIMU/TIMUX 541/556 256
HUNDREDTH-MS TIMER (See note.) TMUH/TMUHX 544/557 259
ACCUMULATIVE TIMER TTIM/TTIMX 087/555 262
LONG TIMER TIML/TIMLX 542/553 266
MULTI-OUTPUT TIMER MTIM/MTIMX 543/554 269
COUNTER CNT/CNTX ---/546 275
REVERSIBLE COUNTER CNTR/CNTRX 012/548 278
RESET TIMER/COUNTER CNR/CNRX 545/547 282