Instruction Functions Section 2-2
COUNTER WAIT
CNTW
814
(BCD)
CNTWX
818
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
CNTW(814)
N
SV
N: Counter
number
SV: Set value
I: Count input
Block program
Required
1209
CNTWX(818)
N
SV
N: Counter
number
SV: Set value
I: Count input
TEN-MS TIMER
WAIT
TMHW
815
(BCD)
TMHWX
817
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
TMHW(815)
N
SV
N: Timer number
SV: Set value
Block program
Required
1212
TMHWX(817)
N
SV
N: Timer number
SV: Set value
Instruction
Mnemonic
Code
Symbol/Operand Function Location
Execution
condition
Page
C
Time elapsed.
Delays execution of the rest of the block program until the specified count
has been achieved. Execution will be continued from the next instruction
after CNTW(814)/CNTWX(818) when the counter counts out.
SV: 0 to 9,999 times for BCD and
0 to 65,535 times for binary
"C"
executed.
"C"
executed.
"C" executed.
"B" executed.
SV
preset.
"A"
executed.
C
BEND
Time elapsed.
Delays execution of the rest of the block program until the specified
time has elapsed. Execution will be continued from the next
instruction after TMHW(815)/TMHWX(818) when the timer times out.
SV: 0 to 99.99 s for BCD
and 0 to 655.35 s for binary
"A"
executed.
SV
preset.
"B" executed.
"C" executed.