478
Symbol Math Instructions Section 3-11
Description /UL(433) divides the unsigned binary values in Dd and Dd+1 by those in Dr
and Dr+1 and outputs the quotient to R, R+1 and the remainder to R+2, and
R+3.
Flags
Precautions When the content of Dr, Dr+1 is 0, the Error Flag will turn ON.
If as a result of the division, the content of R, R+1, is 0000 hex, the Equals
Flag will turn ON.
If as a result of the division, the content of the leftmost bit of R+1 is 1, the Neg-
ative Flag will turn ON.
Examples When CIO 000000 is ON in the following example, D00100 and D00101 will
be divided by D00111 and D00110 as 8-digit unsigned hexadecimal values
EM Area with bank En_00000 to En_32766
(n = 0 to C)
En_00000 to
En_32764
(n = 0 to C)
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants #00000000 to
#FFFFFFFF
(binary)
#00000001 to
#FFFFFFFF
(binary)
---
Data Registers ---
Index Registers ---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Area Dd Dr R
R + 1 RR + 3 R + 2
÷
Dd + 1 Dd
Dr + 1 Dr
Remainder Quotient
(Unsigned binary)
(Unsigned binary)
(Unsigned binary)
Name Label Operation
Error Flag ER ON when the result is 0.
OFF in all other cases.
Equals Flag = ON when as a result of the division R+1, R is 0.
OFF in all other cases.
Negative Flag N ON when the leftmost bit of the R+1, R is 1.
OFF in all other cases.