Symbol Math Instructions Section 3-11
Description /BL(435) divides BCD values in Dd and Dd+1 by those in Dr and Dr+1 and
outputs the quotient to R, R+1 and the remainder to R+2, R+3.
Flags
Precautions If Dd, Dd+1 and/or Dr, Dr+1 are not BCD or the content of Dr, Dr+1 is 0, an
error will be generated and the Error Flag will turn ON.
If as a result of the division, the content of R, R+1 is 00000000 hex, the
Equals Flag will turn ON.
Examples When CIO 000000 is ON in the following example, D00101 and D00100 will
be divided by D00111 and D00110 as 8-digit BCD values and the quotient will
be output to D00121 and D00120 and the remainder to D00123 and D00122.
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants #00000000 to
#99999999
(BCD)
#00000001 to
#99999999
(BCD)
---
Data Registers ---
Index Registers ---
Indirect addressing
using Index Registers
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Area Dd Dr R
Dd + 1
Dr + 1
R + 1 RR + 3
R + 2
(BCD)
(BCD)
(BCD)
÷
Dd
Dr
Remainder
Quotient
Name Label Operation
Error Flag ER ON when Dd, Dd+1 is not BCD.
ON when Dr, Dr +1 is not BCD.
OFF in all other cases.
Equals Flag = ON when the result is 0.
OFF in all other cases.