No. SX-DSV02310 - 158 -
R2.0 Motor Business Division, Appliances Company, Panasonic Corporation
8-1-7 RTEX cyclic data error protection 1/2 (Err. 86.0/Err. 86.1)
Th
is alarm will occur, when data error in cyclic command area (C/R, MAC_ID, cyclic command) occurs or when
Sub_Chk error continues in 32-byte mode for the predetermined period.
Cause Data error occurs in cyclic command area (C/R, MAC_ID, cyclic command) or
Sub_Chk error continues in 32-byte mode for the predetermined period.
Alarm code Detected space Cause
Byte 0. bit 4–0 MAC-ID Not fit with setting on
rotary switch
Byte 0. bit 7 C/R Set at 1
Err. 86.0
Byte 16. bit 7 Sub_Chk Set at 0
Err. 86.1 Byte 1. bit 6–4 Cyclic command Undefined
Detecting timing When RTEX communication status is RUNNING.
When synchronization between the communication and servo is established.
When received data is read at the communication cycle.
Internal process upon
detecting error
Command error occurs while in alarm condition.
Alarm code Detected space Error_Code
Byte 0. bit 4–0 MAC-ID 0011h
Byte 0. bit 7 C/R
Err. 86.0
Byte 16. bit 7 Sub_Chk
0012h
Err. 86.1 Byte 1. bit 6–4 Cyclic command 0021h
For details of command error, see Section 6-9-1.
Discard the received data.
Use the previously received normal data for processing (servo is in alarm
status).
RTEX communication keeps RUNNING status.
Because the communication continues, if the normal reception is possible
after occurrence of alarm, commands such as alarm clear can be received.
Action Check the data in the cyclic command field (Detected space in the table above).
Check the process in the host controller
Alarm clear attribute Can be cleared.
Display on COM LED Flashing in red