No. SX-DSV02310 - 73 -
R2.0 Motor Business Division, Appliances Company, Panasonic Corporation
6-6-2 Setting up of alarm code
W
ith MINAS-A5N series, an alarm code (Alarm_Code) is divided into the main and sub numbers. By using bit 1 of
Pr.7.23 (RTEX function expansion setup 2), however, only the main number can be used as in the case of MINAS-A4N.
Note that both the main and sub number should be specified when reading alarm attribute.
Bit 1 of Pr.7.23
Byte Title
0
(compatible with conventional model)
1
12 Main Main number Main number
13
Alarm_Code
Sub 0 Sub number
6-6-3 Alarm attribute
Byte bit7 6 5 4 3 2 1 0
12 NOT_REC NOT_ACLR EMG-STP - - - - -
13 - - - - - - - -
14 - - - - - - - -
15 - - - - - - - -
NOT_REC: Do not record in alarm history.
NOT_ACLR: Do not clear.
EMG-STP: Enable emergency stop.