Operating the measuring device
“MF1 – Preset” submenu
Main menu →
→ Menu → →Pron→ → more → → MFx
On → → MF1 → → ActSta → → Functn → → Preset
Requirements for display
• “more” menu: “Yes” option
• “MFx On” menu: “Enable” option
• “Functn” parameter: “Preset” option
Parameters Description
sPrset The preset is adopted as an initialization value. If the MF1
multifunctional input is activated, the preset is used.
Adjustment range
• –300,000
to +300,000
Because the display can only handle six digits, only negative
values down to “–99,999” can be input via the display.
Factory setting
• 10
Table 21: “MF1 – Preset” submenu
Setting the preset 1. Select the “Preset” function for the MF1 multifunctional input.
2. Enter the desired initialization value for the “Preset” parameter.
3. Move the vehicle to the initialization position.
4. Activate the MF1 multifunctional input, e.g., using a proximity switch,
a photoelectric sensor, or a switch.
5. The output value of the distance measuring device corresponds to the
set value for “Preset” at the initialization position.