8024484/2019-06-06 • © SICK AG • Subject to change without notice 85
PROFINET IO interface
10.3.3 Module 3: „Speed/i2w”
Type Input module, 2 words, consistent
Description This module reads the currently ascertained speed according to the
selected resolution.
Note If there was no valid measured value due to a device fault, a missing
reectororcontamination,thenthevalue“0”isoutputforthedistance
and the corresponding bits are set in the status bytes.
Input values
Rel. Adr. Description
0 Current speed in selected resolution Depending on the
resolution, a digit corresponds to 0.1 mm/s to 100 mm/s.
Type
Signed 32-bit number in two´s complement
Module parameters
Name Description
Resolution Determines the resolution of the speed value on the PROFINET
interface. 1 digit can correspond to 0.1 mm/s, 1 mm/s,
10 mm/s or 100 mm/s.
Value range
0.1 mm/s
1 mm/s
10 mm/s
100 mm/s
free Speed Resolution [µm/s]
Default value
1 mm/s
Free speed
resolution
Determines the resolution of the speed value on the PROFINET
interface if the “free Speed Resolution [µm/s]” value has been
selected in the “Resolution” parameter.
Value range
1 ... 100,000 µm/s
Default value
1,000 µm/s
10.3.4 Module 4: “Distance/i2w, Speed/i2w”
Type Input module, 4 words, consistent
Description This module reads both the current distance and the currently ascertained
speedinaccordancewiththeselectedresolutionandoset.