8024484/2019-06-06 • © SICK AG • Subject to change without notice 93
PROFINET IO interface
Input values
Rel. Adr. Description
0.0 Bit = 1: Plausibility warning
Measured values are faulty. The likelihood of an error occur-
ring is high.
Type
1 bit
0.1 Bit = 1: Temperature warning
The ambient temperature is only just within the permissible
range. The likelihood of an error occurring is high.
Type
1 bit
0.2 Bit = 1 Signal level warning
The measured signal level is close to the permissible limit.
The likelihood of an error occurring is high.
Type
1 bit
0.3 Bit = 1: Laser warning
The laser has reached the end of its service life. The likelihood
of an error occurring is high.
Type
1 bit
0.4 Bit = 1: Plausibility error
No valid measured value can be calculated.
Type
1 bit
0.5 Bit = 1: Temperature error
Thedeviceisoperatedoutsideofthespeciedtemperature
range.
Type
1 bit
0.6 Bit = 1: Signal level error
The measured signal level is too low.
Type
1 bit
0.7 Bit 1: Laser error
The laser may have reached the end of its service life.
See Page 94, Chapter 10.3.9, operating hours.
Type
1 bit
1.0 Bit=1:Laserswitchedo
1 bit
1.1 Bit = 1: Heater switched on
Type
1 bit