EasyManuals Logo

Siemens 7SR12 Argus User Manual

Siemens 7SR12 Argus
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #130 background imageLoading...
Page #130 background image
7SR11 & 7SR12 Performance Specification
ยฉ2017 Siemens Protection Devices Limited Chapter 3 Page 18 of 56
Section 2: Protection Functions
2.1 27/59 Under/over voltage
2.1.1 Reference
Parameter
Value
V
s
Setting
5, 5.5โ€ฆ200V
hyst
Hysteresis setting 0, 0.1โ€ฆ 80.0%
t
d
Delay setting
0.00, 0.01โ€ฆ20.00, 20.50โ€ฆ 100, 101โ€ฆ 1000, 1010โ€ฆ
10000, 10100โ€ฆ 14400 s
2.1.2 Operate and Reset Level
Attribute Value
V
op
Operate level
100 % Vs, ยฑ 1 % or ยฑ0.25V
Reset level
Overvoltage
= (100 % - hyst) x V
op,
ยฑ 1 % or ยฑ 0.25V
Undervoltage
= (100 % + hyst) x V
op
ยฑ 1 % or ยฑ 0.25V
Repeatability
ยฑ 1 %
Variation
-10 ยฐC to +55 ยฐC
โ‰ค 5 %
f
nom
ยฑ 5 %
โ‰ค 5 %
2.1.3 Operate and Reset Time
Attribute Value
t
basicE
Element basic
operate time
Overvoltage
0 to 1.1 x Vs: 73 ms, ยฑ 10ms
0 to 2.0 xVs: 63 ms, ยฑ 10ms
Undervoltage
1.1 to 0.5 xVs: 58 ms, ยฑ 10ms
t
op
Operate time following delay
t
basic
+ t
d
, ยฑ 1 % or ยฑ 10ms
Repeatability
ยฑ 1 % or ยฑ 10ms
Disengaging time < 80 ms

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 7SR12 Argus and is the answer not in the manual?

Siemens 7SR12 Argus Specifications

General IconGeneral
BrandSiemens
Model7SR12 Argus
CategoryProtection Device
LanguageEnglish

Related product manuals