EasyManuals Logo

Siemens 7SR12 Argus User Manual

Siemens 7SR12 Argus
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #55 background imageLoading...
Page #55 background image
7SR11 & 7SR12 Description Of Operation
ยฉ2017 Siemens Protection Devices Limited Chapter 1 Page 51 of 88
100%
I
I
ฮธ
2
ฮธ
2
F
ร—=
Where: ฮธF = final thermal state before disconnection of device
49 Overload Setting I
ฮธ
is expressed as a multiple of the relay nominal current and is equivalent to the factor k.
IB
as defined in the IEC255-8 thermal operating characteristics. It is the value of current above which 100% of
thermal capacity will be reached after a period of time and it is therefore normally set slightly above the full load
current of the protected device.
The thermal state may be reset from the fascia or externally via a binary input.
Thermal overload protection can be inhibited from:
Inhibit 49 A binary or virtual input.
IL
1
49 Alarm
49 Trip
49 Time Constant
49 Capacity Alarm
49
Overload
Setting
c
cap alarm
trip
IL2
IL3
cap alarm
trip
cap alarm
trip
Inhibit 49
49 Therm. Overload
Enabled
Disabled
&
๏‚ณ1
๏‚ณ1
Reset 49
r
Figure 3-22 Logic Diagram: Thermal Overload Protection (49)
3.10 Current Protection: Line Check 50LC, 50G LC and 50SEF
LC โ€“ Only software option โ€˜Cโ€™
This feature prevents a CB being repeatedly manually closed onto a faulted line. It is enabled upon the
Manual CB Close output being issued.
If a fault is detected following closure, the Relay will trip for Line Check. A fault is detected if the
measured current is above the LC-n Setting level for a period greater than the LC-n Delay.
Two line check elements are provided, LC-1 and LC-2, for each fault type - phase and earth / sensitive earth
โ€“ in the CURRENT PROTโ€™N > LINE CHECK menu.
The feature will remain enabled until the CB has been closed for a duration equal to the Close CB
Pulse + Reclaim Timer settings in the CIRCUIT BREAKER MENU. Alternatively, the element will
remain enabled as long as the Line Check binary input is energised.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 7SR12 Argus and is the answer not in the manual?

Siemens 7SR12 Argus Specifications

General IconGeneral
BrandSiemens
Model7SR12 Argus
CategoryProtection Device
LanguageEnglish

Related product manuals