Siemens 7SR12 Argus - Auto-Reclose Example 3, Simple Single Shot Sequence

Siemens 7SR12 Argus
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR11 & 7SR12 Applications Guide
Page 38 of 48 ©2017 Siemens Protection Devices Limited
4.1.3 Auto-Reclose Example 3, simple single shot sequence
Requirement: Settings shall provide one phase fault reclose for IDMTL or DTL highset- and one reclose for earth
fault IDMTL or DTL highest.
Proposed settings include:
CONTROL & LOGIC > AUTORECLOSE PROT’N:
79 P/F Inst Trips: none
79 E/F Inst Trips: none
79 P/F Delayed Trips: 51-1, 50-1
79 E/F Delayed Trips: 51N-1, 50N-1
79 P/F HS Trips: none
79 E/F HS Trips: none
CONTROL & LOGIC > AUTORECLOSE CONFIG
79 Num Shots: 1
CONTROL & LOGIC > AUTORECLOSE CONFIG > P/F SHOTS
79 P/F Prot’n Trip 1 : Inst (not important as there are no Inst elements set)
79 P/F Prot’n Trip 2 : Delayed (not important as there are no Inst elements set)
79 P/F HS Trips to Lockout : 5 (not used)
79 P/F Delayed Trips to Lockout : 5 (not used)
CONTROL & LOGIC > AUTORECLOSE CONFIG > E/F SHOTS
79 E/F Prot’n Trip 1 : Delayed (not important as there are no Inst elements set)
79 SEF Prot’n Trip 2 : Delayed (not important as there are no Inst elements set)
79 E/F HS Trips to Lockout : 5 (not used)
79 E/F Delayed Trips to Lockout : 5 (not used)