EasyManuals Logo

Siemens 7SR12 Argus User Manual

Siemens 7SR12 Argus
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #389 background imageLoading...
Page #389 background image
7SR11 & 7SR12 Applications Guide
ยฉ2017 Siemens Protection Devices Limited Chapter 7 Page 33 of 48
2.17 Power (32)
Directional power protection is often applied to motor or embedded generator applications to detect loss of load or
loss of generation. For these applications, Real power may be a more appropriate operating quantity.
Power direction can also be used to recognise and record particular network operation arrangements such as
back feeds or embedded generation conditions.
2.18 Sensitive Power (32S)
The CT accuracy should be considered when setting this function for the application.
2.19 Power Factor (55)
Power factor limits can be set to provide alarms or even tripping for abnormal power factor load.
Power factor can also be used to switch in and out additional plant such as capacitors

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 7SR12 Argus and is the answer not in the manual?

Siemens 7SR12 Argus Specifications

General IconGeneral
BrandSiemens
Model7SR12 Argus
CategoryProtection Device
LanguageEnglish

Related product manuals