7SR11 & 7SR12 Performance Specification
ยฉ2017 Siemens Protection Devices Limited Chapter 3 Page 21 of 56
2.4 37 Undercurrent
2.4.1 Reference
Parameter Value
Is
Setting
0.05, 0.10โฆ5.0 xIn
t
d
Delay setting
0.00, 0.01โฆ20.00, 20.10โฆ 100, 101โฆ 1000, 1010โฆ
10000, 10100โฆ 14400 s
2.4.2 Operate and Reset Level
I
op
Operate level
100 % Is, ยฑ 5 % or ยฑ 1% In
Reset level
โค 105 % I
op
Repeatability
ยฑ 1 %
Variation
-10 ยฐC to +55 ยฐC
โค 5 %
f
nom
ยฑ 5 %
โค 5 %
2.4.3 Operate and Reset Time
Attribute Value
t
basic
Element basic operate time
1.1 to 0.5 xIs: 35 ms, ยฑ 10ms
t
op
Operate time following delay
t
basic
+ t
d
, ยฑ 1 % or ยฑ 10ms
Repeatability
ยฑ 1 % or ยฑ 10ms
Overshoot time < 40 ms
Disengaging time < 60 ms