7SR11 & 7SR12 Description Of Operation
Chapter 1 Page 30 of 88 ยฉ2017 Siemens Protection Devices Limited
2.11.1 PROTECTION HEALTHY/DEFECTIVE
When the relay has an auxiliary DC supply and it has successfully passed its self-checking procedure then the
front facia Protection Healthy LED is turned on.
A changeover or open contact can be mapped via the binary output matrix to provide an external protection
healthy signal.
A changeover or closed contact can be mapped via the binary output matrix to provide an external protection
defective signal. With the โ€˜Protection Healthyโ€™ this contact is open. When the auxiliary DC supply is not applied to
the relay or a problem is detected within the relay then this output contact closes to provide external indication.
If the relay is withdrawn from the case, the case shorting contact will make across the normally closed contacts to
provide and external alarm.