EasyManuals Logo

Siemens 7SR12 Argus User Manual

Siemens 7SR12 Argus
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
7SR11 & 7SR12 Description Of Operation
ยฉ2017 Siemens Protection Devices Limited Chapter 1 Page 33 of 88
โ‰ฅ1
Inhibit 50-n
50-n
50-n Setting
c
50-n
Enabled
Disabled
>
c
50-n Delay
If directional elements are not
present this block is omitted and all
'Lx Dir En' signals are set TRUE.
Forward
Reverse
50-n Dir Control
Non-Dir
โ‰ฅ1
&
&
โ‰ฅ1
&
&
โ‰ฅ1
&
&
L1 Dir En
L2 Dir En
L3 Dir En
IL1 Fwd
IL1 Rev
IL2 Fwd
IL2 Rev
IL3 Fwd
IL3 Rev
&
&
&
โ‰ฅ1
โ‰ฅ1
โ‰ฅ1
50-n VTS Action
Off
Non Dir
Inhibit
VT Fail
&
&
>
c
>
c
L1 Dir En
L2 Dir En
L3 Dir En
IL1
IL2
IL3
50/51
Measurement
L1 81HBL2
50-n Inrush
Action
Off
Inhibit
&
L2 81HBL2
L3 81HBL2
&
&
&
&
&
โ‰ฅ1
General Pickup
&
&
79 P/F Inst Trips
= 50-n
79 P/F Protโ€™n Trip n
= Delayed
AUTORECLOSE
Figure 3-2 Logic Diagram: Instantaneous Over-current Element
3.1.3 TIME DELAYED OVERCURRENT PROTECTION (51)
Two time delayed overcurrent elements are provided in the 7SR11 relay and four elements are provided in the
7SR12 relay.
51-1, 51-2, (51-3 & 51-4 โ€“ 7SR12)
51-n Setting sets the pick-up current level. Where the voltage controlled overcurrent function (51VCO) is used a
multiplier is applied to this setting where the voltage drops below the setting VCO Setting, see Section 3.2.
A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is
selected from IEC, ANSI or user specific curves using 51-n Char. A time multiplier is applied to the characteristic
curves using the 51-n Time Mult setting. Alternatively, a definite time lag delay (DTL) can be chosen using 51-n
Char. When Definite Time Lag (DTL) is selected the time multiplier is not applied and the 51-n Delay (DTL)
setting is used instead. The full list of operating curves is given in Chapter 2 โ€“ โ€˜Settings and Instruments Guideโ€™.
Operating curve characteristics are illustrated in Chapter 3 โ€“ โ€˜Performance Specificationโ€™.
The 51-n Reset setting can apply a definite time delayed reset, or when the operation is configured as an IEC or
ANSI or user characteristic if the reset is selected as (IEC/ANSI) DECAYING reset the associated reset curve will
be used. The reset mode is significant where the characteristic has reset before issuing a trip output โ€“ see
โ€˜Applications Guideโ€™.
A minimum operate time for the characteristic can be set using 51-n Min. Operate Time setting.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 7SR12 Argus and is the answer not in the manual?

Siemens 7SR12 Argus Specifications

General IconGeneral
BrandSiemens
Model7SR12 Argus
CategoryProtection Device
LanguageEnglish

Related product manuals