EasyManuals Logo

Siemens 7SR12 Argus User Manual

Siemens 7SR12 Argus
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
7SR11 & 7SR12 Description Of Operation
Chapter 1 Page 38 of 88 ยฉ2017 Siemens Protection Devices Limited
The 51-n Reset setting can apply a definite time delayed reset, or when the operation is configured as an IEC or
ANSI or user characteristic if the reset is selected as IEC/ANSI (DECAYING) reset the associated reset curve will
be used. The reset mode is significant where the characteristic has reset before issuing a trip output โ€“ see
โ€˜Applications Guideโ€™
A minimum operate time for the characteristic can be set using the 51N-n Min. Operate Time setting.
A fixed additional operate time can be added to the characteristic using the 51N-n Follower DTL setting.
Where directional elements are present the direction of operation can be set using 51N-n Dir. Control setting.
Directional logic is provided independently for each 51N-n element.
Operation of the time delayed earth fault elements can be inhibited from:
Inhibit 51N-n A binary or virtual input.
79 E/F Inst Trips: 51N-n When โ€˜delayedโ€™ trips only are allowed in the auto-reclose sequence
(79 E/F Protโ€™n Trip n = Delayed).
50-n Inrush Action: Block Operation of the inrush current detector function.
51N-n VTSAction: Inhibit Operation of the VT Supervision function (7SR1205 & 7SR1206).
General Pickup
51N-
n
51N-n Setting
51N
-
n Charact
51N-n Time Mult
51N
-n Min Operate Time
51N-n Reset
If directional elements are not present this block is
omitted and the '
51N-
n Dir En' signal is set TRUE.
Forward
Reverse
51N-
n Dir.
Control
Non-Dir
โ‰ฅ1
&
&
51N-n Dir En
67N Fwd.
67N Rev
.
51N
-n VTS Action
Off
Non Dir
Inhibit
VT Fail
&
&
&
โ‰ฅ1
IL1
IL2
IL3
I
N
51
N-n Delay
(DTL)
51N-
n Follower DTL
c
Pickup
trip
Inhibit
50
N-n
&
51N-n Element
Enabled
Disabled
81
HBL2
51
N-
n Inrush
Action
Off
Inhibit
&
51N-n Dir En
&
79 P
/F Inst Trips
= 51N-n
79 P/F Protโ€™n Trip n
= Delayed
AUTORECLOSE
Figure 3-7 Logic Diagram: Derived Time Delayed Earth Fault Protection

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 7SR12 Argus and is the answer not in the manual?

Siemens 7SR12 Argus Specifications

General IconGeneral
BrandSiemens
Model7SR12 Argus
CategoryProtection Device
LanguageEnglish

Related product manuals