7SR11 & 7SR12 Performance Specification
ยฉ2017 Siemens Protection Devices Limited Chapter 3 Page 20 of 56
2.3 32S Sensitive Power
2.3.1 Reference
Parameter
Value
S
s
32S-n Setting
0.005โ€ฆ2 x Sn
t
d
32S-n Delay setting 0.00 โ€ฆ 14400 s
2.3.2 Operate and Reset Level
Attribute
Value
S
op
Operate level
100 % Ss, ยฑ 5% or ยฑ 2% Sn
Reset level
Over-power
โ‰ฅ 95 % S
op
Under-power
โ‰ค 105 % S
op
Variation
-10 ยฐC to +55 ยฐC
โ‰ค 5 %
f
nom
โ€“ 3 Hz to f
nom
+ 2 Hz
โ‰ค 5 %
2.3.3 Operate and Reset Time
Attribute Value
t
basicE
Element basic
operate time
Over-power
1.1 x Ss: 60 ms ยฑ 10 ms
2.0 x Ss: 45 ms ยฑ 10ms
Under-power
0.5 x Ss: 30 ms ยฑ 10ms
t
op
Operate time following delay
t
basic
+ t
d
, ยฑ 1 % or ยฑ 10ms
Disengaging time < 40 ms
2.3.4 Operate Threshold
Attribute
Value
Minimum levels for
operation
I 2.5 % In
V 2.5% Vn