7SR11 & 7SR12 Performance Specification
ยฉ2017 Siemens Protection Devices Limited Chapter 3 Page 47 of 56
Attribute Value
t
op
Operate
time
char = IDMTL
[ ]
1
M
t
Vs
0V3
op
โˆ’
=
, ยฑ 5 % or ยฑ 65 ms
char = DTL
t
d
, ยฑ 1 % or ยฑ 40ms
Reset Time
char = IDMTL
t
res
, ยฑ 5 % or ยฑ 65ms
char = DTL
t
res
, ยฑ 1 % or ยฑ 40ms
Repeatability
ยฑ 1 % or ยฑ 20ms
Overshoot time < 40 ms
Disengaging time < 100 ms