Chapter 4 - 7SR120 · Data Communications Definitions
© 2017 Siemens Protection Devices Limited Chapter 4 - Page 51 of 84
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Codes
(dec)
Qualifier Codes
(hex)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
10 1 Binary Output
2 (write) 00, 01 (start-stop)
10
2 (default -
see note 1)
Binary Output
Status
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
11 0
Binary Output Change
- Any Variation
1 (read)
06 (no range, or all)
07, 08 (limited qty)
11 1
Binary Output Change
without Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
11
2 (default -
see note 1)
Binary Output Change
with Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
12 0
Control Relay
Output Block
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
12 1
Control Relay
Output Block
3 (select)
4 (operate)
5 (direct op)
6 (dir. op, noack)
17, 28 (index)
129
(response)
echo of request
12 2
Pattern Control
Block
3 (select)
4 (operate)
5 (direct op)
6 (dir. op, noack)
7 (limited quantity)
129
(response)
echo of request
12 3 Pattern Mask
3 (select)
4 (operate)
5 (direct op)
6 (dir. op, noack)
00, 01 (start-stop)
129
(response)
echo of request
13 0
Binary Output
Command Event
- Any Variation
1 (read)
06 (no range, or all)
07, 08 (limited qty)
13
1 (default -
see note 1)
Binary Output
Command Event
without Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
13 2
Binary Output
Command Event
with Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
20 0
Binary Counter
- Any Variation
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
20 1
32-Bit Binary Counter
(with Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
20 2
16-Bit Binary Counter
(with Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
20 3
32-Bit Delta Counter
(with Flag)
20 4
16-Bit Delta Counter
(with Flag)
20
5 (default
see note 1)
32-Bit Binary Counter
(without Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)