Chapter 4 - 7SR120 ยท Data Communications Definitions
ยฉ 2017 Siemens Protection Devices Limited Chapter 4 - Page 63 of 84
Binary Output Status Points
Static (Steady-State) Object Number: 10
Change Event Object Number: 11
Control Relay Output Blocks (CROB) Object Number: 12
Binary Output Command Event Object Number: 13
Static Variation reported when variation 0 requested: 1 (Binary Output w/o status)
or 2 (Binary Output with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time)
or 2 (Binary Output Event with Time)
Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time)
or 2 (Command Status with Time)
Point
Index
Description
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 10
Default
Variation
Event
Object 11
Default
Command
Event
Object 13
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Command
Event
Object 13
CROB
Supported
Operations
Default
CROB
Operations
1 RL 1 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
2 RL 2 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
3 RL 3 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
4 RL 4 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
5 RL 5 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
6 RL 6 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
7 RL 7 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
8 RL 8 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
33
LED reset, write only
location.
0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
34 Settings Group 1 0 2 2 0 1
Pulse On
Latch On
Close
Latch On
35 Settings Group 2 0 2 2 0 1
Pulse On
Latch On
Close
Latch On
36 Settings Group 3 0 2 2 0 1
Pulse On
Latch On
Close
Latch On
37 Settings Group 4 0 2 2 0 1
Pulse On
Latch On
Close
Latch On
42 Auto-reclose on/off 0 2 2 0 1
Pulse On
Pulse Off
Latch On
Latch Off
Close
Pulse On
Pulse Off
Latch On
Latch Off