FS20 Marine Fire Detection Panel Control Panel
Siemens Industry, Inc. A6V10519176_enUS_b
Building Technologies Division
6.8 Adjustment Elements
S32: Reset key
The 'S32' button has multiple functions depending on how long it is pressed and
whether it is pressed with combinations of other buttons.
Press for <2 s Panel is shut down and restarted in a controlled manner. This
procedure takes up to five minutes.
Press for >2 s Panel is shut down and restarted immediately. This may lead
to data loss. This procedure takes up to two minutes.
Press S32 + 'Reset' or
'Acknowledge' (front operating
buttons) at the same time
Restore factory settings or update firmware.
Restore factory settings
Restoring factory setting will remove all configurations, it is recommended to save the
configuration data before restoring the factory setting.
Press S32 + 'Reset' (front
operating button) for > 2 s at
the same time
Panel is started in Restore factory settings mode.
A short beeping sound confirms the function is being executed.