FS20 Marine Fire Detection Control Panel
Siemens Industry, Inc. A6V10519176_enUS_b
Building Technologies Division
25.6 Commissioning with Manual Configuration and Auto-
Configuration
NOTICE
Commissioning as a Stand-alone ‘Panel’
‘Panels’ commissioned as standalone Panel cannot be combined to form a networked ‘Site’
later on.
• Initialized networked ‘Panel’ using a network address from the beginning.
Prerequisites:
• The detectors circuits and devices are installed.
• The detectors circuits and devices are configured and tested with the ‘Device
programming unit’, DPU.
• The ‘Panel’ is installed.
• The batteries are installed but not connected.
• The cables for the detector circuits and mains supply have been fed into the ‘Panel’
and not connected.
• The configuration tool is installed on the PC.
• The current firmware and BDV are available on the PC.
Commissioning for Standalone ‘Panel’ Variant 1
With commissioning variant, first auto-configures the ‘Panel’, then adapt the auto-configuration
manually in the configuration tool.
1. Prepare the ‘Panel’ for commissioning
2. Perform the auto-configuration
• ‘Auto-configure Panel’ or
• Individually auto-configure detectors circuits
3. Connect the PC to the ‘Panel’.
4. Load the automatically created configuration to the PC.
5. Adapt the configuration in the configuration tool.
6. Load the configuration from the PC to the ‘Panel’.
7. Test the function of the ‘Site’.
8. Rectify errors if necessary and load the corrected configuration from the PC to the ‘Panel’.
9. Disconnect the PC from the ‘Panel’.
10. Perform the competition work.