The values displayed in the "Export jobs for SIMATIC PDM" area are updated.
The icon in the overview screen is updated.
6.4.8.5 How to start the automatic synchronization
Requirement
The faceplate for the parameter data export is open.
Procedure
1. Select the "Automatic synchronization field device --> project" check box.
Result
If a difference in the parameter data between the device and project is detected or if a device
signals a configuration change independently, the complete parameter data are first read from
the device and saved in the project automatically.
The parameter data saved in the project are then exported to the specified destination.
The selected filter criteria are not taken into consideration for the device selection.
The values displayed in the "Export jobs for SIMATIC PDM" are not updated.
An active export job is not indicated in the icon.
A log file is not created on the maintenance station.
6.4.8.6 How to end the automatic synchronization
Requirement
The "Parameter data export" faceplate is open.
Procedure
1. Deselect the "Automatic synchronization field device --> project" check box.
Result
Automatic synchronization in the case of a configuration change has been ended.
Operator control and monitoring
6.4 Functions in the overview screen
Maintenance Station
Function Manual, 03/2016, A5E36187641-AA 109

Table of Contents

Other manuals for Siemens SIMATIC PCS7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS7 and is the answer not in the manual?

Siemens SIMATIC PCS7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS7
CategoryControl Systems
LanguageEnglish

Related product manuals