Additional information
You can find information on error texts in the section "Error texts for field devices/user
objects (Page 180)".
6.11.3.20 Error texts for field devices/user objects
The following table shows possible error texts in the views:
● "Diagnostics" view for field devices (Page 172)
● "Parameters" view for field devices (Page 174)
● "Diagnostics" view for user objects (Page 176)
● "Monitoring" view for user objects (Page 178)
Error code Output In the faceplate Possible measures
A0040110
80010108
Connection to SIMATIC PDM could
not be established.
Possible causes:
- Archiving is active on the ES
- Communication error
- Access to the project is blocked
Check:
● Whether the ES is accessible via the terminal bus
● Whether an archiving job is running on the ES
Wait until the end of the archiving job.
● Whether the SIMATIC PDM Asset Service is stopped and the
"automatic start/stop" is not activated
Allow the "automatic start/stop".
Start the SIMATIC PDM Asset Service.
A0040001 General error has occurred. A general SIMATIC PDM error is indicated.
Contact Technical Support.
A0040006 Internal error - Incorrect call parame‐
ter
The transferred XML string is incorrectly structured.
Contact Technical Support.
A0040101 Command cannot be run because
PDM Asset Service is being stopped.
Check whether the SIMATIC PDM Asset Service is currently being stop‐
ped and "automatic start/stop" is not activated.
Allow the "automatic start/stop" and start the SIMATIC PDM Asset Serv‐
ice.
A0040102 Command cannot be run because
PDM Asset Service is stopped.
A0040103 Internal error - Error when parsing the
XML transfer parameters
The transferred XML string is incorrectly structured.
Contact Technical Support.
A0040002 Not enough memory. Check whether the error is still indicated after a restart of the ES.
A0040104 Maintenance path not found or emp‐
ty.
● Check whether the maintenance project is entered correctly in the
settings for SIMATIC PDM.
● Stop and start the SIMATIC PDM Asset Service.
A0040105 Timeout for current command. Error in the SIMATIC PDM Asset Service when executing the jobs.
Check whether the error is still indicated after a restart of the ES.
A0040106 Internal error - Command could not
be executed
A0040107 Internal error - Timeout for current
command
The SIMATIC PDM Asset Service should be stopped, but this is not
possible because jobs are still queued or are still being processed.
● Wait a little longer.
● Then reboot the computer.
A0040108 PCS 7 project cannot be opened.
● Close SIMATIC Manager on the ES and open the project again.
● Stop and start the SIMATIC PDM Asset Service.
Operator control and monitoring
6.11 Faceplate
Maintenance Station
180 Function Manual, 03/2016, A5E36187641-AA