6.4.9.4 How to start the automatic synchronization (OPC)
Procedure
1. Set the @AssetControl.AdditionalTrigger tag to "1".
Result
When a device configuration change is detected, an automatic synchronization is performed
and an export file is created.
The selected filter criteria are ignored during automatic synchronization.
The automatic synchronization has no effects on the tags @AssetControl.DeviceCount,
@AssetControl.DeviceCountOK and @AssetControl.DeviceCountFailed.
The icon in the overview screen is not updated.
A log file is not created.
6.4.9.5 How to end the automatic synchronization (OPC)
Procedure
1. Set the @AssetControl.AdditionalTriggerRun tag to "0".
Result
Automatic synchronization in the case of a configuration change has been ended.
The @AssetControl.AdditionalTrigger tag is automatically set to "0".
6.4.9.6 How to start the parameter data export for a selected device (OPC)
Procedure
1. Write the @AssetControl.TagExportName tag with the tag name of the device to be
exported.
2. Write the @AssetControl.ExportPath tag.
3. Select which parameter data are exported.
– If you are exporting online parameter data, write the @AssetControl.ActionType tag with
the value 0x01.
– If you are exporting offline parameter data, write the @AssetControl.ActionType tag with
the value 0x02.